Permit: T06PL00255

Parcel: 13304024F


Addresses:

1595 N BROWN AV


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL00255

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 16 PSI TEST FROM METER ABOVE GROUND TO STOVE, WATER HEATER/FURNACE APPROVED
02/17/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE APPROVED COUPLING PRIOR TO FURNACE VALVE IN FURNACE CLOSET.
2. PROVIDE 3-GALV SCREWS AT EACH JOINT OF FLUE VENT PIPING FROM WATER HEATER & FURNACE.
3. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTIN AT CEILING OF FURNACE CLOSET.
4. PROVIDE FULL SIZE RIDGID GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF OR PROVIDE CITY SIGNED ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF APPEAL ON SITE WITH CORRECT INSTALLATION.
5. VENT THRU ROOF TO REMAIN FULL SIZE DOUBLE WALL VENT MATERIAL WITH APPROVED CAP TERMINATIING MINIMUM 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE.
6. REMOVE FUTURE TEE CONNECTION BY MOTOR AND SUPPORT & SECURE PIPING CORRECTLY.