Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06PL00255
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 16 PSI TEST FROM METER ABOVE GROUND TO STOVE, WATER HEATER/FURNACE APPROVED |
|
02/17/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE APPROVED COUPLING PRIOR TO FURNACE VALVE IN FURNACE CLOSET. 2. PROVIDE 3-GALV SCREWS AT EACH JOINT OF FLUE VENT PIPING FROM WATER HEATER & FURNACE. 3. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTIN AT CEILING OF FURNACE CLOSET. 4. PROVIDE FULL SIZE RIDGID GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF OR PROVIDE CITY SIGNED ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF APPEAL ON SITE WITH CORRECT INSTALLATION. 5. VENT THRU ROOF TO REMAIN FULL SIZE DOUBLE WALL VENT MATERIAL WITH APPROVED CAP TERMINATIING MINIMUM 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE. 6. REMOVE FUTURE TEE CONNECTION BY MOTOR AND SUPPORT & SECURE PIPING CORRECTLY. |