Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06PL00249
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2006 | PLUMBING - GAS PRESSURE TEST | Approved | ||
04/07/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 12 PSI TEST FROM METER TO POOL HEATER ONLY. SEE NOTE #1 FROM 2/9/06 |
|
02/09/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE RATED FLEX FOR BTU RATING OF APPLIANCE OR HARD PIPE. 2. PROVIDE ASME RATED PRESSURE RELIEF FOR BTU REQUIREMENTS OF APPLIANCE. 3. READ INSTALLATION REQUIREMENTS OF APPLIANCE THIS APPLIANCE REQUIRES OPENINGS ON THREE SIDE WHEN INSTALLED BELOW A OVERHANG. |