Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* PRESSURE TEST & PIPING OK OK TO COVER OK TO CALL FOR GAS 889-1888 CORRECT WH VENT - INSTALLED UPSIDE DOWN EXTEND TO 1 FOOT ABOVE ROOF RECALL INSPECTION AFTER COMPLETING. |
|
| 02/07/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 8 OR 9 PSI 60 POUND GAGE 2) USE A GAGE WITH 1/10 PSI INCREMENTATION FOR PRESSURE TEST WRAP ALL TOOL MARKS ON SCOTCH CODE-USE PRIMER 2) REMOVE CONCEALED UNION BELOW GRADE 3) CORRECT FLUE PIPING AT WH-TYPE B DBL WALL 4) CORRECT T & P RELIEF AT WH 5) PROVIDE ELECTRICAL BONDING OF GAS LINE |