Permit: T06PL00239

Parcel: 137050830


Addresses:

320 W WYOMING ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/09/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
PRESSURE TEST & PIPING OK
OK TO COVER
OK TO CALL FOR GAS 889-1888
CORRECT WH VENT - INSTALLED UPSIDE DOWN EXTEND TO 1 FOOT ABOVE ROOF
RECALL INSPECTION AFTER COMPLETING.
02/07/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 8 OR 9 PSI 60 POUND GAGE
2) USE A GAGE WITH 1/10 PSI INCREMENTATION FOR PRESSURE TEST WRAP ALL TOOL MARKS ON SCOTCH CODE-USE PRIMER
2) REMOVE CONCEALED UNION BELOW GRADE
3) CORRECT FLUE PIPING AT WH-TYPE B DBL WALL
4) CORRECT T & P RELIEF AT WH
5) PROVIDE ELECTRICAL BONDING OF GAS LINE