Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/09/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
02/07/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAGE READING ZERO-CHECK FOR LEAKS
2) PROVIDE PRESSURE TEST ON SYSTEM
3) AGA GAS VALVES REQUIRED
4) T & P MUST TERMINATE OUTSIDE
5) CAP OR REMOVE TEE AT ABANDON FURNACE VENT LOCATION
6) SEAL WALL PENETRATION
7) PROVIDE ELECTRICAL BONDING OF GAS LINE (GROUND TO WATER)
8) SIZE OF GAS LINE TO ROOF TOP FURNACE IS NOT ADEQUATE 3/4" PIPE WOULD BE REQUIRED TO FURNACE, REDUCE AT APPLIANCE CONNECTION
9) PIPING ON ROOF WILL NEED ADEQUATE SUPPORT