Permit: T06PL00195

Parcel: 124050630


Addresses:

910 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL00195

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2006 PLUMBING - GAS PRESSURE TEST Approved OK FOR GAS -- CALL SW GAS @ 889-1888
02/09/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
PIPING IS TO ROOF TOP FURNACE ONLY
PRESSURE TEST IS OK
PROVIDE WEATHER RESISTANT PIPING SUPPORTS
EVERY 8 FEET AND SECURE WITH CLAMPS
RECALL FOR INSPECTION
02/07/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GO CLOTHING STORE IS 910
POST ADDRESS
- SUPPORT PIPING ROOF
- PIPING RUNS ACROSS ROOF THEN DROPS DOWN INTO SHOP CALLED "DIVAS".
- THIS APPEARS TO SUPPLY GAS TO ONE OF TWO WATER HEATERS
IF THIS IS THE CASE, THEN THE SHUT OFF VALVES WILL NEED TO BE AGA, T&P WILL NEED TO BE CORRECTED, VENT WILL NEED TO BE SECURED.
PLEASE PROVIDE MORE INFORMATION REGARDING WHICH APPLIANCES THAT THIS GAS PIPING IS SUPPLING
02/06/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*THERE ARE MULTIPLE STORE FRONTS, NONE OF WHICH HAVE A POSTED ADDRESS. THE CONTRACTOR IS VERY AWARE OF THE NEED TO HAVE THE ADDRESS POSTED