Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE UPPER COMBUSTION AIR OPENING MIN. 100 SQ. IN 2. PROVIDE PETITION OF APPEAL, OR GRAVITY DRAIN WATER HEATER T&P RELIEF DRAIN TO DAYLIGHT AND TERMINATE VERTICALLY 6-24" ABOVE GROUND. 3. REMOVE TAPE AT VENT CONNECTOR TO VENT TRANSITION SECURE WITH SCREWS. |