Permit: T06PL00155

Parcel: 10603015B


Addresses:

105 E YAVAPAI RD

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
05/04/2007 SITE - SEWER Approved IVRS - Inspection :*
4" BRANCH TO #16-#19 OK TO COVER
CONTRACTOR TO REDLINE ROUTE ON PLAN
04/27/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1. ALL SECTIONS TESTED OK
2. NEED TO SEE FINAL CONNECTIONS
04/20/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
NOT READY FOR INSPECTION
04/11/2007 SITE - SEWER Not ready for Inspection PROVIDE INSPECTION HISTORY FOR SECTIONS NOT NOTED ON INSPECTION HISTORY
04/10/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
04/03/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
REVIEWED W/KAREN
SEWER
04/02/2007 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE PROVIDE INSPECTION HISTORY FOR THE TESTING OF THE PRIVATE SEWER. YOU HAVE NOT BEEN GIVEN PERMISSION TO CONNECT TO BLDGS.
MUST HAVE PLAN AND PERMIT ON SITE FOR INSPECTION
03/27/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
1. PLEASE BE ADVISED WHEN YOU SCHEDULE AN INSPECTION LIKE THIS ESPECIALLY ONE THAT YOU HAVE MADE AN APPOINTMENT FOR - PLEASE BE READY. THE INSPECTOR DOES NOT HAVE TIME TO STAND AROUND WHILE THE TESTERS SET ABOUT PREPARING FOR THE TEST. (THESE GUYS WERE PRETTY FAST).
2. CONTRACTOR SHOULD BE ON SITE. TECHNICALLY I CANNOT DO AN INSPECTION WITHOUT APPROVED PLAN AND PERMIT ON SITE.
3. MANHOLE #2 - 15 SECOND W/LESS THAN ONE POUND DROP. ACTUAL TEST 29 SEC.
MANHOLE #3 - 15 SECONDS W/NO PERCEPTIBLE DROP ACTUAL TEST 29 SEC.
03/08/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
TWO BASES POURED OK
OK TO STACK MANHOLES
03/03/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
1. 8" SDR35 BETWEEN PUBLIC MH #1 AND PRIVATE MH #2 OK
NOTE: 4" BRANCH IS NOT SHOWN ON THE PLAN. CONNECTION TO 8" MADE OK - DO NOT COVER 4"
8" SDR 35 BETWEEN MH #2 AND #3 OK WITH ONE LATERAL INCLUDED.
8" SDR BETWEEN MH #3 AND BCS #3 OK TO COVER SUBJECT TO VERIFICATION OF GRADE
WATER TEST OK THESE SECTIONS
NEED TO SEE BASES AFTER THEY ARE POURED.