Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2006 | PLUMBING - FINAL | Denied | 03050 - 14 PSI TEST FROM METER UNDERGROUND TO EXISTING PIPING AT BUILDING TO DRYER, WATER HEATER, FURNACE OK -- PARTIAL APPROVAL 03090 - COMPLY WITH ITEM #3 FROM 1/26/06 INSPECTION |
|
| 01/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER |
|
| 01/26/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MINIMUM 18" BURIAL DEPTH FOR PLASTIC GAS PIPING. 2. PROVIDE MINIMUM 100 SQ. IN. UPPER & LOWER COMBUSTION AIR OPENINGS FOR WATER HEATER. 3. PROVIDE SEAL FOR BOTTOM OF FURNACE DOOR WHEN CLOSED TO PREVENT PRODUCTS OF COMBUSTION BEING SUCKED INTO RETURN AIR PLENUM. 4. CAP OLD GAS PIPE. 5. SEAL GAS PRESSURE ENTRY INTO BUILDING. |