Permit: T06PL00149

Parcel: 136282290

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/31/2006 PLUMBING - FINAL Denied 03050 - 14 PSI TEST FROM METER UNDERGROUND TO EXISTING PIPING AT BUILDING TO DRYER, WATER HEATER, FURNACE OK -- PARTIAL APPROVAL
03090 - COMPLY WITH ITEM #3 FROM 1/26/06 INSPECTION
01/31/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
01/26/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MINIMUM 18" BURIAL DEPTH FOR PLASTIC GAS PIPING.
2. PROVIDE MINIMUM 100 SQ. IN. UPPER & LOWER COMBUSTION AIR OPENINGS FOR WATER HEATER.
3. PROVIDE SEAL FOR BOTTOM OF FURNACE DOOR WHEN CLOSED TO PREVENT PRODUCTS OF COMBUSTION BEING SUCKED INTO RETURN AIR PLENUM.
4. CAP OLD GAS PIPE.
5. SEAL GAS PRESSURE ENTRY INTO BUILDING.