Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :*15 PSI TEST IS OK ALL CORRECTIONS HAVE BEEN MADE |
|
| 02/08/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 15 PSI TEST IS OK ON PIPE IN TRENCH OK TO BACKFILL. FINISH GAS LINE ABOVE GROUND TO POOL HEATER. BE SURE TO USE PROPER SUPPORT. RETEST SYSTEM. |
|
| 02/02/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE TALLER RISER OR SCOTCH COATED PIPE WITH PRIMED & TAPED COUPLING ON RISER TO 6" ABOVE GRADE AT METER. 2. PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS FOR TESTING. 3. AOBE GRADE PIPING SHALL NOT CREATE A TRIPPING HAZARD AT POOL HEATER LOCATION. PROVIDE FULL SIZE PIPING TO HEATER |