Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* OK FOR GAS |
|
| 02/16/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REPLACE BROKEN T&P RELIEF DRAIN CORRECTION #4 HAS NOT BEEN COMPLETED |
|
| 01/25/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WATER HEATER DRAIN CANNOT BE TRAPPED 1. T&P MUST GRAVITY DRAIN TO EXTERIOR AND TERMINATE 6" - 24" ABOVE GROUND. 2. SECURE VENT CONNECTOR W/SCREWS 3. PROVIDE A MIN. OF 6" OF CLEARANCE BETWEEN SINGLE WALL VENT CONNECTOR AND COMBUSTIBLE MATERIALS. 4. EXTEND FLUE VENT TO 3' ABOVE FORCED AIR INLET 5. PROVIDE ELECTRICAL BONDING OF GAS LINE CALL FOR FINAL INSPECTION AFTER COMPLETING. |