Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :*14 PSI TEST FROM METER TO EXISITING BUILDING ENTRY TO WATER HEATER/ FURNACE /STOVE OK GAS CARD AT METER. |
|
| 01/24/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM TEST PRESSURE AT TIME OF INSPECTION WITH NO PRESSURE LOSS FOR 10 MINUTES 2) PIPING SHALL NOT BE RAN UNDERGROUND UNDER BLDG OR STRUCTURE (BACK PORCH) (OVERHANG) WITHOUT CORRECT SLEEVING PER 2003 UNIFORM PLUMBING CODE 3) PROVIDE AGA OR CSA APPROVED GAS VALVE AT STOVE 4) PROVIDE MINIMUM 100 SQ INCHES LOWER COMBUSTION AIR OPENING FOR FURNACE/WATER HEATER ROOM 5) PROVIDE BONDING OF BLDG GAS PIPING |