Permit: T06PL00122

Parcel: 11901081A


Addresses:

302 W 43RD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/30/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
13.6 PSI PRESSURE TEST OK
OK FOR GAS
01/26/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PSI LESS THAN 5 ON A 30 PSI GAUGE
1. SEC 319.1 ILLUSTRATE TRAINING MANUAL AND VPC REQUIRES THAT PRESSURE TESTS OF 10 PSI OR LESS SHALL BE PERFORMED WITH GAUGES OF 1/10 POUND INCREMENTATION - SEC 319.4 UPC "TEST GAUGES SHALL HAVE A PRESSURE RANGE NOT GREATER THAN TWICE THE TEST PRESSURE APPLIED."
2. T& P SHALL TERMINATE WITHOUT THREADS
3. SECURE WATER HEATER ENCLOSURE IT IS FALLING APART.