Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/25/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 13 PSI TEST FROM NEW METER LOCATION ABOVE GROUND TO EXISTING SERVICE ENTRY TO WATER HEATER/FURNACE & DRYER OK 03090-NOT READY 1. PROVIDE BONDING OF BUILDING GAS PIPING 2. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN CANNOT BE TRAPPED, IT SHALL BE RIGID PIPING GRAVITY DRAIN TO DAYLIGHT 3. VENT FROM WATER HEATER & FURNACE TO BE 3' + 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH APPROVED DOUBLE WALL VENT PIPING + CAP |