Permit: T06PL00111

Parcel: 136390980


Addresses:

4708 S ROSETTE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/14/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
LEFT GAS CARD
03/13/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SECURE GAS PIPING & PLUG DRAIN PAN FOR WATER HEATER
03/10/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RELOCATE HIGH COMBUSTION AIR OPENING.
PROVIDE MAX. 3' FLEX CONNECTORS ON APPLIANCES
15 PSI TEST IS OK
OK TO BACKFILL TRENCH
02/14/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE NEW WATER HEATER ADDED TO PERMIT.
2. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN PIPING SHALL GRAVITY DRAIN TO DAYLIGHT OR OBTAIN SIGNED PETITION OF APPEAL FOR ALTERNATE FORM OF T&P RELIEF ON SITE WITH CORRECT INSTALLATION.
3. GAS PIPING SHALL NOT BE INSTALLED UNDER BUILDING OR STRUCTUE UNLESS INSTALLED IN CORRECT SLOOVING PER CHAPTER 12 2003 UPC.
4. PROVIDE MINIMUM 100 SQ INCH UPPER & LOWER COMBUSTION AIR FOR WATER HEATER.
5. PROVIDE CORRECT BONDING OF BUILDING GAS PIPING.
6. VENTS FROM WATER HEATER & FURNACE SHALL HAVE 3 GALV SCREWS AT EACH JOINT.
7. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION AT FURNACE & WATER HEATER.
8. VENT FROM FURNACE TO BE 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE
9. CHECK YOUR BTU REQUIREMENTS OF APPLIANCES AND VERIFY YOUR PIPE SIZING MEETS THIS REQUIREMENT.