Permit: T06PL00097

Parcel: 10603145A


Addresses:

109 W PRINCE RD #05


Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T06PL00097

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/19/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ROOF FLASHING AT ROOF FOR VENT, UNIT C PROVIDE DOUBLE WALL VENT PIPING FROM ENCLOSURE THRU ROOF WITH APPROVED VENT CAP WITH 3-GALV SCREWS AT EACH JOINT OF VENT PIPING.
2. PROVIDE MINIMUM 100 SQ INCHES UPPER & LOWER COMBUSTION AIR OPENING FOR WATER HEATER.
3. PROVIDE NEW FITTINGS FOR PIPING.
4. SEAL PENETRATIONS INTO BUILDING AROUND GAS PIPING
5. SECURE GAS PIPING IN ATTIC OF UNIT C
6. PROVIDE WATER HEATER PULL SPACE FOR WATER HEATER IN UNIT D