Permit: T06PL00081

Parcel: 135060600


Addresses:

6710 E CALLE LUNA

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
01/18/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NO GAS PIPING SHALL BE UNDEGROUND UNDER STRUCTURE
UNDERGROUND PIPING TO BE SCOTCH COAT INCLUDING RISERS, WITH PRIMER THEN 10 MIL TAPE AT ALL JOINTS & TOL M??
GAS PIPING SYSTEM TO BE TESTED IN ITS ENTIRETY
SECURE GAS PIPING AT WATER HEATER & PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE.
VENT FROM WATER HEATER TO HAVE 1" MINIMUM CLEARANCE FROM PLYWOOD OF ROOF STRUCTURE AND HAVE 3 GALV SCREWS AT EACH JOINT OF VENT PIPING
PROVIDE AGA OR CSA APPROVED GAS VALVE AT FURNACE
PROVIDE BONDING OF BUILDING GAS PIPING