Permit: T06PL00078

Parcel: 131100640


Addresses:

5617 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/11/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
THESE ITEMS ABOVE ARE INSPECTED ON PERMIT# T06CM01385
05/09/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OWNER HAS (2) PERMITS THIS ONE AND #T06CM01325 THIS PERMIT ADDITIONAL DESCRIPTION OF WATER HEATER & WATER LINE ON IT.
T06CM01325 IS FOR WATER LINE AND GAS PIPING.
THIS INSPECTION IS FOR ALL OF ABOVE AND BOTH PERMITS SHALL BE CALLED IN AT REINSPECTION.
03050 -- 15 PSI TEST FROM METER TO HOUSE SERVICE VALVE PARTIAL PROVIDE AGA OR CSA GAS VALVE AT STOVE & RETEST ENTIRE SYSTEM.
1. WATER HEATER SHALL HAVE CORRECT RATED FLEX FOR 140,000 BTU REQUIREMENTS.
2. WATER HEATER T&P DRAIN SHALL GRAVITY TO DAYLIGHT.
3. VENT FROM WATER HEATER TO BE DOUBLE WALL THRU ROOF PENETRATION WITH APPROVED DOUBLE WALL VENT CAP AT TERMINATION.
4. PROVIDE BONDING OF BUILDING GAS PIPING WITH JUMPER FROM INTERIOR WATER PIPING TO EXTERIOR WATER PIPING.
03040 -- 1" COPPER FROM METER TO BUILDING & WATER HEATER OK
1. PROVIDE SHUT OFF VALVE AT METER DISCHARGE.