Permit: T06PL00045

Parcel: 133197080


Addresses:

993 N CARIBE AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/19/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/18/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE REQUIRED TEST GAGE ON LOW PRESSURE GAS SYSTEM IS LB MAX WITH 1/10 INCREMENTS
2. SHALL PROVIDE TAPE PRIMER ON ALL JOINTS UNDERGROUND AND THEN APPLY THE TAPE.
3. SHALL OBTAIN A APPEAL FORM FROM OUR OFFICE FOR ALTERNATE METHOD FOR T&P DRAIN
01/13/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL UNDERGROUND PIPING TO BE SCOTCH COATED, INCLUDING RISERS,
2. PIPE TO BE PRIMED, THEN TAPED AT ALL UNDERGROUND FITTINGS & TOOL MAKRS.
3. PROVIDE GAS ISOMETRIC DRAWING APPROVED BY CITY FOR ANY FUTURE CONNECTION (TEE OUTLET).
4. PROVIDE UPPER & LOWER COMBUSTION AIR MINIMUM 100 SQ. INCHES EACH FOR WATER HEATER.
5. PROVIDE GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF OR SIGNED BY CITY PETITION OF APPEAL FOR ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF ON SITE WITH CORRECT INSTALLATION.
6. PROVIDE BONDING OF BUILDING GAS PIPING.