Permit: T06PL00012

Parcel: 126132830


Addresses:

4625 E 17TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/12/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
01/11/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 12 PSI TEST NOT HOLDING PRESSURE
2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS
3) REMOVE TAPE
4) ALL CRIMPED ENDS TO GO WITH FLOW
5) GAS FLEX CANNOT PENETRATE THE FURNACE CABINET
6) PROVIDE A T & P RELIEF DRAIN SLOPED TO DAYLIGHT
7) PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES
8) BOND THE GAS PIPE WITH ELECTRIC PANEL
9) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON ENTIRE GAS SYSTEM