Inspection History Details
Inspection Status: Denied
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK FLUORESCENT CABINET 1. SUPPORT MC CABLES AS PER CODE AND NOT OFF OF ONE ANOTHER 2. PROPERLY LABEL CIRCUIT DIRECTORY 3. MAINTAIN WORKING CLEARANCES AT PANELS 110.26 |
|