Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 03/09/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* | |
| 03/07/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE COLORS FOR 277V 2. CORRECTLY INSTALL GROUND WIRE UNDER GROUND SCREW. 3. SPLICES TO BE LISTED FOR WET LOCATION 4. TIGHTEN LOOSE FITTINGS 5. FINISH PREVIOUS ITEM |
|
| 03/06/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* HECTOR TO RESCHEDULE |
|
| 02/27/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK WALL SIGNS 1. CHANGE 277 VOLT CONDUCTORS AS DISCUSSED |
|
| 02/26/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 02/09/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK SHOP FOR 5X12 SIGN |
|
| 02/06/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEPERATE GTO AND MAINTAIN CLEARANCES 2) ISOLATE POWER TO SWITCH 3) USE 277 VOLT COLORS FOR CONDUCTORS |
|
| 02/01/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 01/31/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* |