Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 11/28/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY PLUMB SINK & DISHWASHER 2. REVERSE PRESSURE BACKFLOW REQUIRED FOR CARBONATORS. 3. REMOVE KEYED DEADBOLT @ PATIO (WHEELCHAIR MAN/WOMAN BRAILLE SIGNS REQUIRED FOR RESTROOMS. |
|
| 11/03/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: THIS IS NOT A COMPLETE LIST. ALL REQUIRED BACKFLOW, INDIRECT & DIRECT WASTE ETC. STILL NEEDS TO BE VERIFIED. 1. H.C SIGNS FOR PARKING TO BE MOUNTED 84" ABOVE GRADE. 2. PROVIDE PERMITS AND INSPECTION HISTORY FOR NEW COLD BOX AND NEW WATER HEATER. 3. ALL EQUIPMENT MUST BE IN AND READY FOR INSPECTION A C OF O INSPECTION IS FOR WHEN YOU ARE READY TO OPEN. 4. ALL EMERGENCY LIGHTING MUST WORK. 5. GATES OFF PATIO TO SWING OUT. NO DOORS EXCEPT MAIN ENTRANCE MAY HAVE KEYED LOCKS FROM EGRESS SIDE. IF YOU WANT THEM TO LOCK YOU NEED PANIC HARDWARE (SECTION 1008 OF IBC) 6. ACCESSIBLE SIGNAGE; ACCESSIBLE HARDWARE & INSULATION KITS ON DRAINS ARE REQUIRED FOR RESTROOMS. 7. MAIN ENTRANCE REQUIRES LEVEL LANDINGS THAT MEET ACCESSIBILITY PROVISIONS OF IBC. |