Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T06OT02807
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2010 | SIGN ELECTRIC | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
03/13/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROTECT PVC ABOVE GRADE OR USE SCHEDULE 80 2. NO MORE THAN 360 DEG. IN A CONDUIT RUN 3. TIGHTEN GROUND SCREW 4. SPLICES TO BE WEATHERPROOF 5. PLEASE VERIFY LISTING FOR PULL BOX 6. NEED PLANS AND PERMIT ON SITE. |