Permit: T06OT02729

Parcel: 136261300

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
01/11/2007 SIGN ELECTRIC Approved IVRS - Inspection :*
OK SIGN
12/15/2006 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING JUNCTION BOX COVER
2. FILL UNUSED OPENING IN ENCLOSURES & LETTERS
3. TIGHTEN LOOSE FITTINGS ENCLOSURES & LETTERS
4. PROVIDE A SERVICE LIGHTS 210.7(C)
5. MAINTAIN GTO CLEARANCES - 1 1/2"
6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.
7. A MARKING LABEL IS NEEDED 600.4
8. NEED CITY STICKERS ON SITE
9. WALKWAY TO HAVE 12" MINIMUM ENTIRE LENGTH.