Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 04/19/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MARKING LABELS ARE NEEDED 2. SPLICES TO BE LISTED FOR WET LOCATION 3. TIGHTEN LOOSE FITTINGS 4. CONNECT GROUNDS TO GROUNDING EQUIPMENT CONDUCTOR OF CIRCUIT 5. REVISE PLANS FOR FLUORESCENT CABINET 6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |