Permit: T06OT02672

Parcel: 10816008B


Addresses:

4980 N 1ST AV

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
04/30/2007 SIGN SHOP Approved IVRS - Inspection :*
04/19/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MARKING LABELS ARE NEEDED
2. SPLICES TO BE LISTED FOR WET LOCATION
3. TIGHTEN LOOSE FITTINGS
4. CONNECT GROUNDS TO GROUNDING EQUIPMENT CONDUCTOR OF CIRCUIT
5. REVISE PLANS FOR FLUORESCENT CABINET
6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.