Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* "PRIMO" 1. NEEDS A MARKING LABEL 600.4 2. BOND LETTERS 600.7 3. PROTECT GTO FROM SHARP METAL EDGES OF PASS THRU'S 300.4 4. A SERVICE LIGHT IS NEEDED 210.70 OK MONUMENT SIGNS |
|
| 08/14/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK 3 AT FIRST ENTRANCE 1. NEED PLANS, PERMIT & CITY STICKERS |
|
| 08/01/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SPLICE CONNECTIONS TO BE FOR WET LOCATION 2. COMPLETE #1, 2, 3 & 5 OF PREVIOUS INSPECTIONS 3. REMOVE INTERNAL SWITCH |
|
| 07/27/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT PVC CONDUIT 2. SUPPORT M/C CABLE 3. TIGHTEN LOOSE FITTINGS 4. SWITCH TO BE EXTREMELY OPERABLE 600.6 |
|
| 07/11/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SIGN SWITCH TO BE WEATHERPROOF 2. PRIMARY CONDUCTORS TO BE ISOLATED TO SWITCH 3. GROUND JUNCTION BOX 4. SECURE SIGN 5. FILL OUT MARKING LABEL 6. CONDUCTOR TO BE COLOR CODED TO VOLTAGES |