Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 11/16/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* NEED MARKING LABELS |
|
| 11/15/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. SWITCH IF NOT WITHIN SIGHT OF SIGN TO BE CAPABLE OF BEING LOCKED OUT 600.6 2. NEED MARKING LABELS PER 600.4 3. GROUND JUNCTION BOXES 250.148 & 600.7 4. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. RECEIVED MONEY ORDER #55581644569 FOR $108.00 |