Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT02439
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* OK C OF O |
|
| 10/03/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST "DOOR TO REMAIN UNLOCKED..." ON FRONT DOOR 2. PLUG RECEPTACLE BY HOOD (OVER SINK) TO BE GFCI PROTECTED. 3. HOOD EXTINGUISHING SYSTEM MUST BE CURRENTLY INSPECTED. 4. EMERGENCY EXIT LIGHTS MUST BE OPERABLE. 5. WATER HEATER IN BACK MUST HAVE TPRV DISCHARGE LINE 6. DISHWASHWER AND SANITIZER SINK MUST BE INDIRECTLY WASTED. 7. PREP. SINK TO BE INDIRECTLY WASTED. 8. ALL INDIRECT WASTE BEHIND BAR TO TERMINATE 1" ABOVE FLOOR SINK. 9. REVERSE PRESSURE BACKFLOW ASSEMBLY REQUIRED FOR CARBONATOR. |