Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T06OT02412
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
02/28/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NO WORK PROGRESS |
|
02/14/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* CEILING NOT RATED FOR WALKING WEIGHT NEED ACCESS TO POWER SUPPLIES |
|
01/23/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
01/18/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PLAN REVISIONS -LETERS ARE NOT SELF CONTAINED MONUMENT 1. WE HAVE EXPOSED CONDUCTORS 2. PROTECT CONDUCTORS FROM SCREWS 3. UE CORRECT SIZED STRAPS PHARMACY 1. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING WEST SIGN 1. USE APPROVED FITTINGS WITH SEAL TITE 2. POWER SUPPLIES TO BE ACCESSIBLE |
|
12/12/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS - WAIT UNTIL FINISHED |
|
12/11/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* | |
11/29/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. ISOLATE POWER TO SWITCH. 2. PLAN SHOWS LARGE LETTERS AS SELF CONTAINED LED. 3. PLEASE VERIFY LED'S FOR USE -- NOT IN SAM MANUAL. 4. BOND METAL LETTERS. 5. POWER SUPPLIES LIMITED TO 40C TEMPERATURE PER SAM |