Permit: T06OT02412

Parcel: 12901044D


Addresses:

1940 E BROADWAY BL


Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T06OT02412

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 SIGN SHOP Approved IVRS - Inspection :*
02/28/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NO WORK PROGRESS
02/14/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
CEILING NOT RATED FOR WALKING WEIGHT
NEED ACCESS TO POWER SUPPLIES
01/23/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
01/18/2007 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PLAN REVISIONS -LETERS ARE NOT SELF CONTAINED

MONUMENT
1. WE HAVE EXPOSED CONDUCTORS
2. PROTECT CONDUCTORS FROM SCREWS
3. UE CORRECT SIZED STRAPS

PHARMACY
1. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING

WEST SIGN
1. USE APPROVED FITTINGS WITH SEAL TITE
2. POWER SUPPLIES TO BE ACCESSIBLE
12/12/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
NO WORK PROGRESS - WAIT UNTIL FINISHED
12/11/2006 SIGN SHOP Partial Approval IVRS - Inspection :*
11/29/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1. ISOLATE POWER TO SWITCH.
2. PLAN SHOWS LARGE LETTERS AS SELF CONTAINED LED.
3. PLEASE VERIFY LED'S FOR USE -- NOT IN SAM MANUAL.
4. BOND METAL LETTERS.
5. POWER SUPPLIES LIMITED TO 40C TEMPERATURE PER SAM