Inspection History: SIGN SHOP

Permit Number - T06OT02381

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2007 SIGN SHOP Approved IVRS - Inspection :*
11/27/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROVIDE WALKWAY ABOVE DRIVE THRU 600.21
2) PROVIDE SERVICE LIGHT 210.70
3) BOX OVER FILLED
4) SWITCH TO BE PER 600.6
5) FINISH PREVIOUS INSPECTION ITEMS DATED 10/04/07
6) MAINTAIN GTO CLEARANCES
03/15/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
OK LETTER SETS WEST SIDE
1. SUPPORT M/C CABLE WITHIN 12" OF BOXES.
2. TIGHTEN LOOSE FITTINGS.
03/08/2007 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE HAVE SIGN CONTRACTOR PRESENT TO ACCESS SIGNS
10/04/2006 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
15" PHOTO CENTER -- 2 SETS
12" RX DRIVE THRU -- 2 SETS

1. USE AN EFFECTIVE GROUND PATH FOR JUNCTION BOXES
2. INSTALL LOCKNUTS FOR FITTINGS & POWER SUPPLIES
3. TIGHTEN LOOSE FITTINGS
4. USE APPROVED FITTINGS
5. GTO CABLE CUT TO CONDUCTOR.