Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T06OT02381
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
11/27/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROVIDE WALKWAY ABOVE DRIVE THRU 600.21 2) PROVIDE SERVICE LIGHT 210.70 3) BOX OVER FILLED 4) SWITCH TO BE PER 600.6 5) FINISH PREVIOUS INSPECTION ITEMS DATED 10/04/07 6) MAINTAIN GTO CLEARANCES |
|
03/15/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK LETTER SETS WEST SIDE 1. SUPPORT M/C CABLE WITHIN 12" OF BOXES. 2. TIGHTEN LOOSE FITTINGS. |
|
03/08/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE HAVE SIGN CONTRACTOR PRESENT TO ACCESS SIGNS |
|
10/04/2006 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 15" PHOTO CENTER -- 2 SETS 12" RX DRIVE THRU -- 2 SETS 1. USE AN EFFECTIVE GROUND PATH FOR JUNCTION BOXES 2. INSTALL LOCKNUTS FOR FITTINGS & POWER SUPPLIES 3. TIGHTEN LOOSE FITTINGS 4. USE APPROVED FITTINGS 5. GTO CABLE CUT TO CONDUCTOR. |