Permit: T06OT02267

Parcel: 11005318D

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
03/01/2007 SIGN SHOP Approved IVRS - Inspection :*
02/07/2007 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ISOLATE POWER TO SWITCH
2) USE APPROVED SPLICE CONNECTORS FOR GROUNDS
3) CONNECT LETTER GROUNDS TO SYSTEM GROUND
4) BOND METAL LETTERS AND NUMBERS
5) TIGHTEN STRAIN RELIEF CONNECTORS
6) VERIFY LEDS FOR LISTING-NO MARKING ON STRIPS
7) SWITCH NOT WORKING
8) A MARKING LABEL IS NEEDED 600.4
01/23/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
08/30/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
WIRING IN WALL FOR BUILDING -- BUILDING LOCKED