Permit: T06OT02266

Parcel: 11521017H

Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T06OT02266

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2007 SIGN SHOP Approved IVRS - Inspection :*
03/06/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
SCOTT CANCELLED
NO WORK PROGRESS
02/26/2007 SIGN SHOP Cancelled CANCELLED PER ANDI #747-1274
02/26/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
11/17/2006 SIGN SHOP Partial Approval IVRS - Inspection :*
1. CIRCUIT CONDUIT TO SIGN TO BE INDEPENDENTLY SUPPORTED 300.11 ALSO, USE APPROVED SUPPORTS.
2. SUPPORT JUNCTION BOX.
11/13/2006 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SIGN REQUIRES A DISCONNECT - NEC 600.6
2. HAVE UNUSED OPENING IN BRANCH CKT. J-BOX
NEC 110.12 (A)
3. CLEAN UP WIRING (BONDING & LOW VOLTAGE WIRING) IN CEILING AND PROTECT.