Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T06OT02223
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
09/08/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. TRANSFORMER TO BE ACCESSIBLE 600.21 2. MENU SWITCH TO BE EXTERNALLY OPERABLE 600.6 3. SWITCH CAPABLE TO BE LOCKED OUT WHEN NOT ON SIGN 600.6 4. SUPPORT NEON SIGN CABLE (POWER PRO) 5. M/C CABLE TO TERMINATE |
|
08/30/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. ISOLATE POWER TO SWITCH 2. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. OK NEON LETTERS |