Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT02205
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2007 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
08/30/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 12" ADDRESS DISPLAY PER PIMA COUNTY ORDINANCE REQUIRED 2. ELECTRICAL DISCONNECTS NOT PROPERLY MOUNTED TO WALL OUTSIDE 3. ALL OPENINGS INTO OUTLETS AND DISCONNECTS MUST BE CAPPED. 4. ATMOSPHERIC VACUUM BREAKERS REQUIRED ON HOSE BIBBS. 5. REMOVE OR REPAIR EMERGENCY EGRESS LIGHTING. 6. CARBONATORS REQUIRE REVERSE PRESSURE BACKFLOW ASSEMBLIES INSTALLED AND CERTIFIED BY QUALIFIED PLUMBING CONTRACTOR. 7. RESTROOMS REQUIRE ACCESSIBLE W.C (17'-19' SEAT HEIGHT FLUSH HANDLE ON WIDE SIDE OF ROOM SPLIT SEAT) ACCESSIBLE LAVATORY (34" MAX HEIGHT, 27" KNEE CLEARANCE) BEVELED THRESHOLD AND ACCESSIBLE DOOR HARDWARE (LEVER HANDLE, AUTOMATIC UNLOCK) 8. ACCESSIBLE SIGNAGE REQUIRED FOR HANDICAP PARKING AND FOR RESTROOMS. 9. PAINT OUT SIDE WALK FOR ACCESSIBLE PATH FROM PARKING TO SEATING AREA. |
|
08/24/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ADDRESS POSTED COULD NOT LOCATE |