Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
01/25/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. GROUNDING/BONDING OF LETTER NOT ALLOWED TO BE SOLDER - 250.8 NEC 18.6 VL 48 |
|
01/23/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. A MARKING LABEL IS NEEDED ON SIGN 600.4 2. WEATHERPROOF WIRING TO LED LETTERS 3. BOND METAL LED LETTERS 4. TIGHTEN LOOSE FITTINGS 5. RACEWAY TO BE COMPLETE - 4 SIDES 6. BOND RACEWAY 7. POWER SUPPLIES FOR INDOOR ONLY 8. POWER SUPPLY TO BE ACCESSIBLE 9. NO PLANS OR PERMIT ON SITE 10. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
09/29/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* |