Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
Permit Number - T06OT02075
Inspection Description - SIGN SHOP
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. FINISH PREVIOUS ROOF ITEMS 2. LOOSE FITTINGS/MISSING LOCKNUT 3. MISSING JUNCTION BOX COVERS OK SMALL LETTER SETS EAST SIDE (4) |
|
03/14/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* ROOF: 1. JUNCTION BOXES NEED TO BE ACCESSIBLE 2. FILL UNUSED OPENINGS 3. USE CORRECT SIZED EMT STRAPS OK LETTER SETS SOUTH SIDE OF BUILDING 7 SIGNS & ARROW |
|
10/25/2006 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE GREEN BONDING CONDUCTOR IN THE SIGN HANDY BOXES USED FOR SWITCHING, REQUIRES A PROPER FITTING IN THE FORM OF A STAKON, SPADE OR OTHER APPROVED MEANS TO SECURE THE STRANDED GREEN WIRE AROUND A SCREWHEAD. 2. ITEMS 2 AND 3 ABOVE NEED TO BE CORRECTED EVEN THOUGH THE SIGN IS UL LISTED. |
|
10/23/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* WILL RESCHEDULE |
|
10/04/2006 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ARROW 12" RX 15" DRIVE THRU 1. USE AN EFFECTIVE GROUND PATH FOR JUNCTION BOXES. 2. INSTALL LOCKNUT FOR FITTINGS AND POWER SUPPLIES 3. PROPERLY MOUNT POWER SUPPLY TO JUNCTION BOX. |