Permit: T06OT02075

Parcel: 12511251A


Addresses:

615 N ALVERNON WY


Inspection Status: Partial Approval

Inspection History: SIGN SHOP

Permit Number - T06OT02075

Inspection Description - SIGN SHOP

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/22/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
1. FINISH PREVIOUS ROOF ITEMS
2. LOOSE FITTINGS/MISSING LOCKNUT
3. MISSING JUNCTION BOX COVERS

OK SMALL LETTER SETS EAST SIDE (4)
03/14/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
ROOF:
1. JUNCTION BOXES NEED TO BE ACCESSIBLE
2. FILL UNUSED OPENINGS
3. USE CORRECT SIZED EMT STRAPS

OK LETTER SETS SOUTH SIDE OF BUILDING 7 SIGNS & ARROW
10/25/2006 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE GREEN BONDING CONDUCTOR IN THE SIGN HANDY BOXES USED FOR SWITCHING, REQUIRES A PROPER FITTING IN THE FORM OF A STAKON, SPADE OR OTHER APPROVED MEANS TO SECURE THE STRANDED GREEN WIRE AROUND A SCREWHEAD.
2. ITEMS 2 AND 3 ABOVE NEED TO BE CORRECTED EVEN THOUGH THE SIGN IS UL LISTED.
10/23/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
WILL RESCHEDULE
10/04/2006 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ARROW
12" RX
15" DRIVE THRU
1. USE AN EFFECTIVE GROUND PATH FOR JUNCTION BOXES.
2. INSTALL LOCKNUT FOR FITTINGS AND POWER SUPPLIES
3. PROPERLY MOUNT POWER SUPPLY TO JUNCTION BOX.