Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT02073
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 09/05/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC CONDENSOR OVER FUSED CURRENTLY HAS 50 AMP FUSES 23.7 IS MIN. WITH 40 MAX. 2. PATCH HOLE IN FLOOR AND HOLES IN WALLS MADE WHEN PLUMBING & ELECTRIC WAS CAPPED |
|
| 08/17/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3" TALL ADDRESS # REQUIRED TO IDENTIFY SUITE 2. ATMOSPHERIC VACUUM BREAKERS REQUIRED AT EXTERIOR HOSE BIBBS. 3. SUPPORT ELECTRIC CONDUITS OFF ROOF AT 10' O.C MAX 4. REPAIR EXTERIOR ELECTRIC CONDUITS. 5. REMOVE EXCESSIVE TREE LITTER AROUND ELECTRIC SERVICES 6. WATER TIGHT COVER REQUIRED FOR PLUG RECEPTACLE @ FRONT 7. A/C CONDENSOR IS OVERFUSED - 40 AMP HACR MAX CURRENTLY FUSED @ 60 AMP. 8. PROPERLY CAP ANY UNUSED PLUMBING AND ELECTRIC. MASSAGE LICENSES WILL REQUIRE SIGNS IDENTIFYING IT AS MASSAGE. |