Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT02034
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
08/07/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 12" ADDRESS DISPLAY PER PIMA COUNTY ORDINANACE REQUIRED. 2. PROPERLY COVER EXTERIOR OUTLET @ SE CORNER USE "BUBBLE" COVER FOR EXTERIOR WET LOCATION. 3. CONNECT DRAIN @ DISHWASHER 4. ALL INDIRECT WASTE DRAINS MUST TERMINATE MINIMUM 1" ABOVE FLOOD RIM OF FLOOR SINKS. 5. NON-CODE COMPLIANT ELEVATED FLOOR SINK @ EAST END OF BAR MUST BE TRAPPED AND PROPERLY DRAINED (CORRECT PITCH) 6. PROPERLY PITCH ALL DRAIN PIPING 7. REVERSE PRESSURE ASSEMBLY REQUIRED FOR BACKFLOW PROTECTION AT CARBONATOR 8. BACK PITCH ON 2" VENT OUTSIDE EAST END OF BAR MUST BE CORRECTED. 9. SPLIT FRONT TOILET SEATS REQUIRED IN RESTROOMS. 10. HAVE ALL UNUSED ELECTRIC OUTLETS PROPERLY COVERED. |