Permit: T06OT02034


Addresses:

222 S CHURCH AV


Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Permit Number - T06OT02034

Inspection Description - CERTIFICATE OF OCCUPANCY

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2006 CERTIFICATE OF OCCUPANCY Approved IVRS - Inspection :*
08/07/2006 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 12" ADDRESS DISPLAY PER PIMA COUNTY ORDINANACE REQUIRED.
2. PROPERLY COVER EXTERIOR OUTLET @ SE CORNER USE "BUBBLE" COVER FOR EXTERIOR WET LOCATION.
3. CONNECT DRAIN @ DISHWASHER
4. ALL INDIRECT WASTE DRAINS MUST TERMINATE MINIMUM 1" ABOVE FLOOD RIM OF FLOOR SINKS.
5. NON-CODE COMPLIANT ELEVATED FLOOR SINK @ EAST END OF BAR MUST BE TRAPPED AND PROPERLY DRAINED (CORRECT PITCH)
6. PROPERLY PITCH ALL DRAIN PIPING
7. REVERSE PRESSURE ASSEMBLY REQUIRED FOR BACKFLOW PROTECTION AT CARBONATOR
8. BACK PITCH ON 2" VENT OUTSIDE EAST END OF BAR MUST BE CORRECTED.
9. SPLIT FRONT TOILET SEATS REQUIRED IN RESTROOMS.
10. HAVE ALL UNUSED ELECTRIC OUTLETS PROPERLY COVERED.