Permit: T06OT02032

Parcel: 10511061R

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
10/05/2006 SIGN SHOP Approved IVRS - Inspection :*
09/29/2006 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PARKING LABEL NEEDED ON SIGN
2. NEED PLANS & PERMIT ON SITE
3. POWER SUPPLY HAS A CUT CORD -- PLEASE VERIFY LISTING OF POWER SUPPLY 56HG - E239831 QILI POWER
4. INSTALL ALL CONDUCTORS UNDER WIRE NUT.
5. USE APPROVED FITTING FOR M/C CABLES
6. MAIN JUNCTION BOX SHEETMETAL SCREW NOT ALLOWED FOR GROUNDING.