Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT01984
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 08/11/2006 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 9:08 AM NO ACCESS |
|
| 08/07/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* #1 - 15" ADDRESS DISPLAY REQUIRED MUST BE VISIBLE FROM STREET #8 - MAXIMUM 5 LBS. PULL ALLOWED FOR RESTROOM DOOR ADJUST YOUR CLOSET #9 - ACCESSIBLE SIGNAGE REQUIRED FOR RESTROOM MOUNT 60" FROM FLOOR AT LATCH SIDE OF DOORWAY. 1" TALL LETTERS (MINIMUM SIZE) AT ENTRANCE/EXIT "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" |
|
| 08/02/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 15" ADDRESS DISPLAY PER PIMA COUNTY ORDINANCE REQUIRED. 2. LEVER HANDLE "ACCESSIBLE" HARDWARE REQUIRED @ 3 DEG. DOOR BY COUNTER AND AT RESTROOM. 3. REMOVE SURFACE MOUNTED LOCKS @ REAR DOOR 4. RESTROOM TO HAVE INSULATION KIT ON LAVATORY DRAIN 5. RESTROOM LAVATORY TO HAVE LEVER OR PUSH HANDLES PER ANSI 117.1 6. IDENTIFY ALL CIRCUITS @ SUB-PANEL 7. I NEED TO VERIFY EMERGENCY EGRESS LIGHTING 8. MAXIMUM 5LBS. PULL ALLOWED ON RESTROOM DOOR. 9. ACCESSBILE SIGNAL REQUIRED AT RESTROOM. 10. FLUSH HANDLE FOR WATER CLOSET TO BE ON "WIDE" SIDE OF ROOM |