Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 03/12/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS |
|
| 03/07/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PLEASE HAVE SIGN CONTRACTOR PRESENT TO ACCESS SIGN |
|
| 09/26/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. FILL UNUSED OPENING IN BACK OF RACEWAY. 2. ONLY ONE CONDUCTOR TO GROUND TERMINAL 3. BOXES OVERFILLLED 312.16 4. FINISH PREVIOUS ITEMS. |
|
| 09/18/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* USE AN EFFECTIVE GROUND FAULT PATH |
|
| 09/15/2006 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN GTO CLEARANCES 2. PROPERLY GROUND RACEWAY 3. ISOLATE PRIMARY POWER CONDUCTOR TO SWITCH 4. CAUTIONARY LABELS PAINTED OVER |