Permit: T06OT01875

Parcel: 124041020

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
01/12/2007 SIGN SHOP Approved IVRS - Inspection :*
01/10/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1. FLEX CONDUIT TO HAVE A GROUNDING EQUIPMENT CONDUCTOR PER AMENDMENTS.
2. FILL UNUSED OPENINGS IN BOX 110.12
3. A MARKING LABEL IS NEEDED 600.4
4. GROUNDS TO BE MINIMUM 1 1/2" AWAY FROM GTO CABLES