Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2009 | SIGN SHOP | Approved | ||
| 09/26/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PVC CONDUIT TO BE AS PER 300.5 18" DEEP ENTIRE LENGTH 2. PLEASE VERIFY NO MORE THAN 360 DEG. IN A RUN 3. PROTECT EMT CONDUIT FROM CORROSION 300.7 4. TIGHTEN LOOSE FITTINGS 5. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119 6. FILL UNUSED OPENING IN BOTTOM OF GUTTER |
|
| 01/02/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS |
|
| 12/29/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) NO POWER TO SIGN-LEAVE TRENCH FOR INSPECTION-NOTE 600.5 2) DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR 3) OK CABINET |