Permit: T06OT01779

Parcel: 12215312A

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
07/10/2009 SIGN SHOP Approved
09/26/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PVC CONDUIT TO BE AS PER 300.5 18" DEEP ENTIRE LENGTH
2. PLEASE VERIFY NO MORE THAN 360 DEG. IN A RUN
3. PROTECT EMT CONDUIT FROM CORROSION 300.7
4. TIGHTEN LOOSE FITTINGS
5. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119
6. FILL UNUSED OPENING IN BOTTOM OF GUTTER
01/02/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
NO WORK PROGRESS
12/29/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1) NO POWER TO SIGN-LEAVE TRENCH FOR INSPECTION-NOTE 600.5
2) DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR
3) OK CABINET