Inspection History Details
Permit: T06OT01512
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 09/22/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. ACCESS HOLE TO BE 2'X2" MINIMUM 2. ACCESS TO BE AS PER 600.21 NEED WALKWAYS FROM ACCESS ENTRANCE TO POWER SUPPLIES. 3. WE HAVE BOX OVERFILL 4. POWER SPULLIES AND SPLICES TO BE AS PER SAN MANUEL REQUIREMENTS. 5. A MARKING LABEL IS NEEDED ON SIGN 600.4 |
|
| 09/21/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 07/17/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* NOTES: 1. WEATHERPROOF LOW VOLTAGE CABLES. 2. MAKE UP TO BE IN JUNCTION BOXES 3. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |