Permit: T06OT01488

Parcel: 12613018A

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T06OT01488

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
06/23/2006 PLUMBING - FINAL Not ready for Inspection 1. WASH & RINSE CAN BE COMBINED BUT SANITIZE BOWL AT 3-COMP SINK TO BE SEPARATE FROM WASH & RINSE.
2. PROVIDE VACUUM BREAKER AT HOSE BIB UNDER
3-COMP SINK.
3. SPRAY HOSE AT 3-COMP SINK TO HAVE CORRECT BACKFLOW
PROTECTION OR BE SPRING TYPE DEVICE TO NOT LET
THERE BE A POSSIBILITY OF SUBMERGED INLET.
4. DRAINS FROM ICE MACHINE TO BE SEPERATE FOR BIN STORAGE & CONDENSATE.
5. ICE MACHINE TO HAVE BACKFLOW PROTECTION FOR WATER INLET OR PROOF OF 1" AIR GAP.
6. SODA DISPENSER WATER SUPPLY SHALL HAVE REDUCED PRESSURE PRINCIPAL BACKFLOW DEVICE FOR CARBONATOR, AND DOUBLE CHECK BACKFLOW PREVENTOR FOR NON-CARBONATED WATER SUPPLY.
7. ALL BACKFLOW DEVICES IN HOUSE TO BE CERTIFIED.
8. ALL INDIRECT DRAINS TO HAVE 1" MINIMUM AIR GAP.