Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T06OT01488
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2006 | PLUMBING - FINAL | Not ready for Inspection | 1. WASH & RINSE CAN BE COMBINED BUT SANITIZE BOWL AT 3-COMP SINK TO BE SEPARATE FROM WASH & RINSE. 2. PROVIDE VACUUM BREAKER AT HOSE BIB UNDER 3-COMP SINK. 3. SPRAY HOSE AT 3-COMP SINK TO HAVE CORRECT BACKFLOW PROTECTION OR BE SPRING TYPE DEVICE TO NOT LET THERE BE A POSSIBILITY OF SUBMERGED INLET. 4. DRAINS FROM ICE MACHINE TO BE SEPERATE FOR BIN STORAGE & CONDENSATE. 5. ICE MACHINE TO HAVE BACKFLOW PROTECTION FOR WATER INLET OR PROOF OF 1" AIR GAP. 6. SODA DISPENSER WATER SUPPLY SHALL HAVE REDUCED PRESSURE PRINCIPAL BACKFLOW DEVICE FOR CARBONATOR, AND DOUBLE CHECK BACKFLOW PREVENTOR FOR NON-CARBONATED WATER SUPPLY. 7. ALL BACKFLOW DEVICES IN HOUSE TO BE CERTIFIED. 8. ALL INDIRECT DRAINS TO HAVE 1" MINIMUM AIR GAP. |