Permit: T06OT01446

Parcel: 129120030


Addresses:

1201 E 26TH ST

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
10/25/2006 SIGN SHOP Approved IVRS - Inspection :*
10/12/2006 SIGN SHOP Partial Approval IVRS - Inspection :*
09/27/2006 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE UNCOVER CONDUIT TO INSPECT
2. VERIFY CIRCUIT IS AS PER 600.5
3. MISSING JUNCTION BOX COVER
4. FILL UNUSED OPENING IN JUNCTION BOX
5. SHEET METAL SCREWS NOT ALLOWED FOR
GROUNDING 250.8
6. PLEASE HAVE PLANS AND PERMIT ON SITE.