Permit: T06OT01336

Parcel: 12407040B


Addresses:

745 E 9TH ST

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
10/25/2006 SIGN SHOP Approved IVRS - Inspection :*
10/18/2006 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
- CORRECTIONS HAVE NOT BEEN COMPLETED.
- MAKE SURE LABEL MARKINGS ARE SUITABLE FOR ENVIRONMENT.
- REINSPECTION FEE WILL BE CHARGED IF NOT CORRECT NEXT INSPECTION.
10/12/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1. MARKING LABELS NEED FOR ALL SIGNS 600.4
2. TIGHTEN HIGH VOLTAGE TERMINALS
3. SHEETMETAL SCREWS NOT ALLOWED FOR
GROUNDING 250.8
4. BOND & GROUND ALL LED LETTERS 600.7
5. DO NOT ENERGIZE SIGNS UNTIL FINALED BY ELECTRICAL INSPECTOR PLEASE DE-ENERGIZE SIGNS UNTIL FINALED.

OK (LOGO) "ACE STORES"