Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T06OT01183
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
06/26/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) NEED MARKING LABEL 600.4 2) SWITCH TO RECEPTACLE OF BEING LOCKED OUT 600.6 3) TIGHTEN LOOSE FITTINGS AND PAS THRU 4) USE APPROVED FITTINGS WITH SEAL TITE 5) GROUND JUNCTION BOXES AND ENCLOSURERS 6) SUPPORT JUNCTION BOXES 7) PLEASE PROVIDE ACCESS TO OPEN LETTERS |