Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06OT01135

Parcel: 13219017F


Addresses:

4881 S CAMPBELL AV


Inspection Status: Denied

Inspection History: SIGN ELECTRIC

Permit Number - T06OT01135

Inspection Description - SIGN ELECTRIC

Inspection Status - Denied

Date Description Inspector Results Comments
01/24/2007 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. A MARKING LABEL IS NEEDED 600.4
2. A SWITCH IS NEEDED AS PER 600.6
ALSO, ISOLATED PRIMARY AS PER PLANS.
3. SECURE SIGN TO WALL WITH CORRECT
HARDWARE NOT DRYWALL SCREWS
4. PLEASE VERIFY SIGN CIRCUITS AS PER 600.5
5. NEED PLAN, PERMIT CARD & CITY STICKERS WITH PAPERWORK ON SITE.

FRED COMBS CONSTR
480-756-0188