Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. A MARKING LABEL IS NEEDED 600.4 2. A SWITCH IS NEEDED AS PER 600.6 ALSO, ISOLATED PRIMARY AS PER PLANS. 3. SECURE SIGN TO WALL WITH CORRECT HARDWARE NOT DRYWALL SCREWS 4. PLEASE VERIFY SIGN CIRCUITS AS PER 600.5 5. NEED PLAN, PERMIT CARD & CITY STICKERS WITH PAPERWORK ON SITE. FRED COMBS CONSTR 480-756-0188 |