Permit: T06OT01030


Addresses:

3202 N ORACLE RD

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
03/03/2008 SIGN SHOP Approved IVRS - Inspection :*
02/28/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WALKWAY TO BE ACCESSIBLE FOR WORKING ON SIGN
2. SERVICE LIGHTS ARE NEEDED
3. SWITCHES TO BE CAPABLE OF BEING LOCKED OUT
4. FILL UNUSED OPENING IN BOX
02/20/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
06/09/2006 SIGN SHOP Partial Approval IVRS - Inspection :*
OK BONDING FOR LETTERS
1. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.
2. NEED MARKING LABEL.